case 950:

As for case 600 except that control strategy has been changed to
"27,V:
-cooling is on from 07.00h to 18.00h if temp. > 27oC
& cooling is off from 18.00h to 07.00h
-heating is always off
Moreover additional  infiltration rate of 13.14ac/h is included (equivalent to
10.8 ac/h at sea level - see BESTEST manual page 1-11) from 18.00h to 07.00h 
(when the vent fan is on).


Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	   0 (0)		  439 (693)


Results (all loads in kW)
-----------
timesteps       Peak heating load                Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	   0     		         2.2 (2 Sep@13h52)


Diff 950-650
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	   -		    -4858 
 DM (1993)	   -		    -4429


Diff 950-650
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	    -  	 	         -4.24
 DM (1993)	    -			 -3.998



Diff 950-900
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	   -		    -1871 
 DM (1993)	   -		    -1745


Diff 950-900
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	   -     	 	 -0.88
 DM (1993)	   -		         -0.855