case 940:

As for case 900 except that temperature control strategy has been changed to
"SETBACK":
-cooling always on if temp. > 27oC
-heating is on from 23.00h to 07.00h if temp. < 10oC
& heating is on from 07.00h to 23.00h if temp. < 20oC


Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	  747 (897)		 2255 (3013)


Results (all loads in kW)
-----------
timesteps       Peak heating load                Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 4.66 (4 Jan@06h52)    		 3.08 (17 Oct@14h07)

Diff 940-640
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-1989		    -4192 
 DM (1993)	-1958		    -3873


Diff 940-640
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -1.2   	 	 -3.45
 DM (1993)	 -1.252			 -3.273



Diff 940-900
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	 -361		      -55 
 DM (1993)	 -377		      -53


Diff 940-900
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  1.8     	 	  0
 DM (1993)	  1.13		          0