case 610:

As for case 600 except that there is a south horizontal overhang.

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	4326(3807)		 4954 (2749)


Results (all loads in kW)
-----------
timesteps       Peak heating load                Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 3.45 (4 Jan@04h37)		 6.10 (25 Nov@12h52)


Diff 610-600
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	   34		    -1685 
 DM (1993)	   59		    -2222


Diff 610-600
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0     	 	 -0.46
 DM (1993)	  0			 -0.525



Diff 910-610
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-3002		    -3732 
 DM (1993)	-2780		    -3094


Diff 910-610
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.58     	 	 -3.62
 DM (1993)	  0.579			 -3.773