case 410:

As for case 400 except that infiltration rate of 0.5 ac/h is included
(equivalent to 0.41 ac/h at sea level - see BESTEST manual page 1-5).

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	8664(7378)		  0 (0)


Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 3.66 (4 Jan@00h52)		 0


Diff 410-400
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	 1994		 	0
 DM (1993)	 1696			0


Diff 410-400
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.77		 	  0
 DM (1993)	  0.758			  0