case 320:

As for case 270 except that the cooling se4tpoint temperature is now 27oC
instead of 20oC

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	3852(3950)		5492 (2685)


Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 2.88 (4 Jan@04h37)		6.01 (25 Jan@12h22)


Diff 320-270
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	 -647		       -2499
 DM (1993)	 -651		       -2467


Diff 320-270
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0		 	 -0.67
 DM (1993)	 -0.002			 -0.655