case 230:

As for case 220 except that infiltration rate of 1ac/h
is included (equivalent to 0.822 ac/h at sea level - see
BESTEST manual page 1-5).

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		10444 (7489)		439 (1271)

Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 4.43 (4 Jan@00h52)     	1.05 (11 Aug@13h07)
 
 
Diff 230-220:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	3430			-265
 DM (1993)	3432			-268

Diff 230-220
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  1.54		 	  0.47
 DM (1993)	  1.519			  0.499