case 220:

As for case 200 except that all internal and external
surfaces have emissivity of 0.9 instead of 0.1.

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		7014 (7772)		174 (988)


Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 2.89 (4 Jan@00h52)     	0.58 (11 Aug@13h22)
 

Diff 220-215:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	1463			-473
 DM (1993)	1397			-453


Diff 220-215
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.08		 	 -0.44
 DM (1993)	  0.08			 -0.447



Diff 220-210:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	504			25
 DM (1993)	488			24


Diff 220-210
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.16		 	  0.11
 DM (1993)	  0.166			  0.084


 
Diff 230-220:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	3430			-265
 DM (1993)	3432			-268


Diff 230-220
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  1.54		 	  0.47
 DM (1993)	  1.519			  0.499



Diff 240-220:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-1302			221
 DM (1993)	-1295			229


Diff 240-220
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.18		 	  0.18
 DM (1993)	 -0.182 		  0.179



Diff 250-220:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-2223			3087
 DM (1993)	-2193			3027


Diff 250-220
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.01		 	  2.82
 DM (1993)	 -0.001 		  2.8




Diff 270-220
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-2513		 	7815
 DM (1993)	-2434			7342


Diff 270-220
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.01		 	  6.1
 DM (1993)	 -0.004 		  5.796



Sensitivity:
------------
 heating energy  diff   cooling energy  diff	simulation
-----------------------------------------------------------
  6933		-81	    194		+20	exposure setting 6 to 3 (rural unobstructed to rural typical)
						- as for case 195, but now with ext emissivity = 0.9