case 200:

As for case 195 except that the area for the windows is covered by "opaque glass"
 i.e. a high conductivity construction (see section 1.4.7)

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		5250 (6785)		574 (1975)

Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 2.68 (4 Jan@00h52)     	0.87 (16 Aug@13h37)



Diff 200-195
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	 1085		 	 158
 DM (1993)	 1085			 156


Diff 200-195
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.67		 	  0.21
 DM (1993)	  0.647			  0.212



Diff 210-200
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	1260			-425
 DM (1993)	1204			-408


Diff 210-200
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.05		 	 -0.4
 DM (1993)	  0.05			 -0.387



Diff 215-200:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	301			73
 DM (1993)	295			69


Diff 215-200
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.13		 	  0.15
 DM (1993)	  0.136			  0.144