case 810:

As for case 800 except:
a) the windows now have transparent glass with optical properties as defined
in Tables 1-7, 1-8 and 1-21.
b) all internal surfaces have absorptivities of 0.1 (and ext absorptivity same
as before: 0.6)


Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	  1754 (2394)		 1128 (2042)


Results (all loads in kW)
-----------
timesteps       Peak heating load                Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 2.99 (4 Jan@06h37)    		 1.96 (2 Sep@13h37)


Diff 900-810
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	 -646		 	1182
 DM (1993)	 -669			1080


Diff 900-810
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.13		 	  1.12
 DM (1993)	 -0.129			  1.036