case 620:

As for case 600 except that there are 2 windows: 1 in the east wall and 1 in the
west wall instead of the window(s) in the south


Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	  4521(3929)		 3800 (2508)


Results (all loads in kW)
-----------
timesteps       Peak heating load                Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 3.61 (4 Jan@06h22)		  4.12 (15 Aug@15h07)

Diff 620-600
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	  229		    -2839 
 DM (1993)	  317		    -2720


Diff 620-600
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.16  	 	 -2.44
 DM (1993)	  0.154			 -2.56



Diff 630-620
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	  261		    -1015 
 DM (1993)	  437		    -1288
 

Diff 630-620
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0     	 	 -0.46
 DM (1993)	  0.001			 -0.562



Diff 920-620
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-1387		    -1710 
 DM (1993)	-1300		    -1577


Diff 920-620
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.31     	 	 -1.53
 DM (1993)	 -0.283		         -1.249