case 430:

As for case 420 except that all external surfaces 
have absorptivity of 0.6 instead of 0.1.


Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	5452(4968)		 537 (1105)


Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 3.47 (4 Jan@00h52)		 1.52 (16 Aug@13h22)


Diff 430-420
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-1907		      528
 DM (1993)	-1869		      531


Diff 430-420
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.01		 	  1.27