case 420:

As for case 410 except that nternal gains of 200W
are included (60% radiative/ 40% convective)


Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour	7359(6729)		 9 (98)


Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 3.48 (4 Jan@00h52)		 0.25  (Jul@15h07)


Diff 420-410
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-1305		 	9
 DM (1993)	-1298		       11


Diff 420-410
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.18		 	  0.250
 DM (1993)	 -0.182			  0.223