case 310:

As for case 300 except that there are 2 overhangs - 1 in each window (west and
east).

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		4931(5246)		3497 (3334)

Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 3.03 (4 Jan@06h22)		3.39 (26 Jul@15h22)


Diff 310-300
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	264		 	-1184
 DM (1993)	460			-1570


Diff 310-300
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.15		 	 -2.84
 DM (1993)	  0.151			 -2.952