case 300:

As for case 270 except that there are 2 windows: 1 in the east wall and 1 in the
west wall instead of the window(s) in the south

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		4667(5085)		4681 (3675)


Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 3.03 (4 Jan@06h22)		3.84 (26 Jul@15h22)


Diff 300-270
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	168		 	-3310
 DM (1993)	251			-3226


Diff 300-270
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.15		 	 -0.45
 DM (1993)	  0.151			 -0.556					
 										
							
							
							
Diff 310-300
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	264		 	-1184
 DM (1993)	460			-1570


Diff 310-300
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0.15		 	 -2.84
 DM (1993)	  0.151			 -2.952