case 290:

As for case 270 except that there is a south horizontal overhang.

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		4533(5018)		6286 (3742)

Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 2.88 (4 Jan@04h37)		6.66 (25 Jan@12h07)


Diff 290-270
Date:		heating energy    cooling energy	
--------------------------------------------------------
 02/8/04	34		 	-1705
 DM (1993)	67			-2324


Diff 290-270
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 02/8/04	  0		 	 -0.02
 DM (1993)	  0			 -0.087