case 280:

As for case 270 except that all int surfaces have 0.1 absorptivity.

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		4664(5189)		5237 (3571)

Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 2.88 (4 Jan@04h37)		4.71 (17 Oct@12h37)


Diff 280-270
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	163		 	-2752
 DM (1993)	165			-2655


Diff 280-270
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	  0		 	 -1.97
 DM (1993)	  0.001 		 -1.912