case 240:

As for case 220 except that internal gains of 200W
are included (60% radiative/ 40% convective)

Results (all energy in kWh)
-----------
timesteps    	 heating energy (hrs)   cooling energy(hrs)
------------------------------------------------
 4 ts/hour		5712 (7021)		395 (1739)


Results (all loads in kW)
-----------
timesteps       Peak heating load               Peak cooling load
---------------------------------------------------------------------------
 4 ts/hour	 2.71 (4 Jan@00h52)     	0.76 (11 Aug@13h22)
 

Diff 240-220:
Date:		heating energy    cooling energy
------------------------------------------------
 28/7/04	-1302			221
 DM (1993)	-1295			229


Diff 240-220
Date:	       Peak Heating          Peak cooling
--------------------------------------------------------
 28/7/04	 -0.18		 	  0.18
 DM (1993)	 -0.182 		  0.179