Indoor
air quality is one of the most important aspects of occupant comfort in site
accommodation for construction villages. In order to provide a safe, healthy and
comfortable indoor environment, minimum ventilation standard need to be provided
depending on the pattern of occupancy and functionality of the accommodation.
Ventilation is required for one or more of the following purposes:
-
provision of fresh air for breathing
-
dilution and removal of airborne pollutants including
odours
-
control of excess humidity (arising from water vapour in
the indoor air)
-
provision of air for fuel burning appliances
-
provides a mean to control thermal comfort.
Ventilation system
is needed in an enclosed building to satisfy health, comfort and cooling needs.
It will be best provided with a good degree of local control. According to the
CIBSE Building Guide, the minimum required fresh air is 5 l/s per person (or 0.5
l/(s m2) while the recommended rate is 8 l/s per person (or 0.8 l/(s
m2). Unsatisfactory internal air quality in a cabin will happen with
too little fresh air. However, with too much ventilation, unnecessary heat
losses will occur with a waste of energy.
An enclosed space
can be provided with natural or mechanical ventilation, depending on the
condition and the environment. Natural ventilation which uses the pressure
differential of the air can be provided with very low capital and operating
costs. It has no mechanical or running parts therefore less maintenance as well
as noise pollution. However, external environment conditions may limit or
prevent the use of natural ventilation. For example, a high level of noise or
pollutants especially in a construction site.
This will then
require the use of mechanical ventilation system. It requires smaller openings,
provides controllability and security as compared with natural ventilation. The
disadvantage of mechanical ventilation is that it consumes electricity and cools
the air. Therefore, mechanical ventilation should be kept to a minimum of the
acceptable levels of indoor air quality.
Providing more
ventilation than is really required increases costs. This is because internal
‘conditioned’ (heated or cooled) air that is removed from a building has to be
replaced with the same amount of air from outside. This also needs to be heated
or cooled to match the temperature of the building. Besides, moving air around
mechanically, using fans uses electricity. Therefore, it is important to
determine the actual requirements and to design a ventilation system that suits
the specific functionality of the accommodations in construction villages.
Back to
Top
The objective of
this part of the project is to propose a methodology to identify the minimum
requirements and standards for ventilation for different types of cabin
accommodation to improve the indoor air quality and the comfort level for the
occupants. In addition to that, further analysis is conducted to recommend low
energy solutions for each accommodation type.
Back to
Top
 |
The
methodology of this study is divided into two parts
-
To evaluate the required ventilation rate that satisfy the
minimum standards for each type of accommodations
-
To select the best possible ventilation system and control
solutions based on identified requirements, energy demand and costs
|
i)
Evaluation of the required ventilation rate
In order to
determine the level of ventilation required, it is important to identify the
conditions of the surrounding, the kind of activity being carried out and the
level of occupancy in the cabin accommodation. There are five factors that will
influence the design of the ventilation system requirement in a cabin
accommodation as shown in the figure above. The five factors described in detail are:
1)
External Air Quality
The external
environment is an important factor to be considered when designing a ventilation
system. Noise level, ambient air temperature and pollution from dust and smoke
will determine if natural ventilation would be possible.
2)
Occupancy Levels
Occupancy levels
will determine the amount of air change that is required for a cabin
accommodation depending on the standard minimum requirements to satisfy health,
comfort and cooling needs of occupants. According to the CIBSE Building Guide,
the minimum required fresh air is 5 l/s per person (or 0.5 l/(s m2)
while the recommended rate is 8 l/s per person (or 0.8 l/(s m2).
3)
Occupancy Activity
The type of
activity people does in the cabin accommodation will also determine the required
air change rates and the ventilation system required. People moving around
require more air than those who are stationary.
4)
Relative Humidity Level
Some specific
accommodation such as the drying room in construction villages need ventilation
to control the humidity level and for creating air flow to dry clothes.
5)
Indoor Pollutants
The types of
equipments and materials used indoor will also emit pollutants such as from
synthetic carpets, photocopying machines, fresh paints, etc. which will need a
higher fresh air to remove those pollutants that poses health threat to
workers.
ii)
Selection of best options of ventilation system and control solutions
Low energy design
shall be considered when designing the ventilation system to the requirements
determined from the first part of the methodology. By designing the system as
close to the required air change rate as possible will prevent excess of
ventilation which will cause wastage of energy. The following are the design
strategies that can be used when designing ventilation system for cabin
accommodations.
1)
Consider natural ventilation first
Natural ventilation does not require any mechanical components or
power and therefore require little or no energy at all. It depends
on the pressure differential of the external and internal
environment to provide the natural air change. However, poor
external air quality and heat losses could cause discomfort and the
increase in heating load.
2)
Mechanical ventilation
Mechanical ventilation can be provided by a fan system at
varying air change rate depending on requirements. The fan can be
chosen according to the air change requirements calculated for the
specified area, occupancy level and occupancy activity.
3) Mechanical ventilation with heat recovery
In
addition to the ventilation fan, it is possible to have a heat
recovery system that can reduce the cost of conditioning or heating
the incoming air by recovering some energy from warm or cool exhaust
air. This system will cost more but the efficiency in heat recovery
would give less heat losses and reduce the heating demand.
4)
Ventilation system controls
Energy
savings can be enhanced further by matching flow rates to demand and
introducing control to the operating times. Ventilation rates may
not need to be constant throughout the day, especially if building
occupation varies during operating hours. Variable-speed fans
controlled by levels of CO2 or process pollutants can be
used. As the need for ventilation increases, fan speeds increase and
more air is brought in. Below are some different control strategies
that could be used for different purpose.
a.
Control with on/off occupancy sensor
Ventilation control using occupancy sensor will operate when the
sensor detects occupancy and will reduce the ventilation rates
during periods of non-occupancy or low level of process activity.
Sensors can monitor and control ventilation rates, meeting occupant
safety and process requirements and minimizing energy consumption.
This system could best used in places such as toilets and store
rooms in construction villages where there are only occasionally
occupied and for a short duration.
|

|
b.
Control with Carbon Dioxide sensor
The
levels of CO2 are monitored and ventilation rates
increase as CO2 levels rise. The level of CO2
is a good indicator of the per-person ventilation rate, since its
presence depends on the number of people in a space and the rate at
which the air in the space is being diluted with outdoor air. This
system controls the outside air volume by regulating CO2
levels. When the CO2 level in the area reaches a
predetermined level, an electronic controller adjusts the
ventilation rates accordingly. This type of system is more precise
than occupancy sensors, as it can adjust for different rates of
occupancy demand, based on levels of physical activity, age and
health. Ventilation control based on CO2 levels is an
important tool that can help control occupant-related pollutants and
satisfy occupant-based ventilation standards. This control type is
very effective in meeting rooms and canteen of construction villages
with varying occupancy pattern all the time. The most common
application measurement of indoor air for CO2 concentration is
typically less than 1,000 PPM in properly ventilated buildings.
Note: Air
Composition
Fresh air contains 21% oxygen and 0.03% carbon dioxide.
Expired air is typically 16% oxygen and 4% carbon dioxide.
CO2 levels > 5% (50000 ppm), acute danger to health (also if
O2 < 12%)
CO2 levels > 0.35% (3500 ppm), long term health implications
CO2 levels > 0.1% (1000 ppm), poor comfort
c.
Control with humidity sensor
Humidity control
increase ventilation rates when internal humidity levels rise. The system uses a
humidistat that can be set to the required humidity level to be maintained as
required. This control is effective in the drying room of construction villages
by maintaining the required humidity level so as to prevent air saturation which
deters clothes from drying.
Back to
Top
This case study is
conducted to determine the minimum ventilation requirement of a standard cabin
accommodation design that serves different functions based on the building
standards mentioned in the introduction. Knowing the requirements, ventilation
systems and control options are proposed for the different cabin functions.
i)
Evaluation of ventilation rate requirements
Assumptions
-
A typical standard cabin with a size of 9.5m x 3.0m x
2.5m high is used for analysis.
-
The minimum required fresh air is 5 litres per second
per person while the recommended rate is 8 litres per second per person.
-
The external air quality depends on the location of the
accommodation in the construction site and the amount of noise and pollution
level at site. In typical construction sites, pollution from dust, airborne
particles and noise are common. Therefore, it is common to minimize the use
of uncontrolled natural ventilation for site accommodations.
|
Accommodation
|
Ventilation Rate Requirements |
Cabin
Offices
 |
There will
be 2 offices in a cabin which can house 2 workers each. So there will be
4 workers whose activities are quite stationary doing desk job and
assuming the offices are occupied 80% of the time. The minimum required
fresh air rate will then be 20 l/s for the whole cabin during office
hours which translates to about 1 air change per hour (AC/hr). The
recommended air change rate will be 1.6 AC/hr.
|
Meeting
Room
 |
A meeting
room of this size can accommodate up to about 10 people at any one time.
The number of people and duration of use will vary a lot in this room
and it is assumed that it will be occupied 40% of the time during office
hours. The minimum fresh air rate will be 2.5 AC/hr with a recommended
4.0 AC/hr for 10 people.
|
Toilets
and Washing Area
 |
This area
will normally be inhabited but will need fresh air to remove odours at
very intermittent intervals. The occupancy rate is assumed to be 20% of
the total working hours. The minimum fresh air rate is recommended to be
about 2 to 4 AC/hr.
|
Canteen
 |
The
canteen area where workers have their meals and rest need to be well
ventilated. One cabin of this size can fit about 24 workers when fully
occupied during tea and lunch time. At other times, there will be
cleaners and some guests around. It is assumed that the canteen will be
occupied 30% of the working time. The minimum fresh air rate for the
maximum number of occupants will be about 6 AC/hr with a recommended
rate of 10 AC/hr.
|
Canteen
Kitchen
 |
The
kitchen area in average will have about 5 workers doing some cooking and
food preparation during the canteen operating hours from 8.00am to
4.00pm. Heavy cooking requires a more intense ventilation to prevent
moisture build-up and dispersing of smoke. Due to the intense activity
requirement, a minimum ventilation rate of about 20 AC/hr is required
with 40 AC/hr recommended.
|
Drying
Room
 |
Ventilation in the drying room is needed for the purpose of controlling
the excess humidity to avoid saturation when the water evaporates from
the wet clothing and to make sure clothes dry within the specified time.
In order for the clothing to dry between 1700 and 0730 the next day, the
temperature and relative humidity of the room is to be maintained at
20ºC and 30% respectively with an air extraction rate of 157 m3/hour
or 2.2 AC/hr |
|
|
|
Determining the
Ventilation Requirements of Accommodation Types |
|
Drying Room
Ventilation Requirements
This study is
conducted to determine the minimum ventilation requirement for a standard drying
room.
Assumptions
i) Every working day, 0.25 litres of water on each set of clothes are
brought in to the drying room and there are 40 sets of clothes to be dried in
the drying room of standard size.
ii) The
clothes need to be dried overnight from 1700 to 0730 the next day.
Analysis
i) Total
amount of water to be evaporated = 0.25 litres x 40 sets = 10 litres
ii) Total
time required = 14.5 hours
iii) The
evaporation/dehumification rate required = 10/14.5 = 0.69 litres/hour
Increase in the
air temperature will cause increase of vapour pressure, increase moisture
content and therefore delayed the saturation of the air in the room. Warm air
can hold more moisture than cold air before reaching the saturation point. With
the air temperature in the drying room maintained at 20ºC, the relative humidity
can be maintained if the water vapour produced is removed from the air at the
rate equal to the evaporation rate of the water vapour from the clothing.
Assuming temperature of 20ºC and relative humidity of 30% is
maintained. From psychometric chart of moisture and temperature, the
water content of air is 0.0044 kg/kg of dry air. Taking the size of
the drying room to be the standard cabin size of 9.5m x 3.0m x 2.5m
high with a volume of 71.25m3, the water content of the
drying room air will be 0.314 litres.
|
 |
 |
Therefore, in order for the clothing to dry between 1700 and 0730
the next day, the temperature and relative humidity of the room is
to be maintained at 20ºC and 30% respectively with an air extraction
rate of 157 m3/hour or more.
|
ii)
Selection of Ventilation System and Control Options
The
selection methods are based on the methodology as described in the methodology
section.
|
Minimum Ventilation Requirements (Recommend)
AC/hr*
|
Flow rate required
m3/hr
|
Ventilation System and Control Options with Low Energy Design
|
Investment / Cost**
£ |
Average Estimated Energy Use per annum**
kWh/year |
Cabin Offices |
1.0
(1.6) |
71.25
(114) |
With the small requirement in offices (< 2 AC/hr), natural
ventilation can be used and the opening and closing of
windows and doors manually is sufficient to provide the
required fresh air rate.
|
Nil |
Nil |
Meeting Room |
2.5
(4.0) |
178.1
(285) |
Option 1: Natural ventilation can be used if the door is to
be left
open for meeting duration.
Option 2: If meetings are to be conducted with closed door
for more than 1 hour with 10 people or more, then
ventilation fan with flow rate of 180 to 285 m3/hr
with heat recovery is recommended.
- Ventilation system to be fitted with controls with
occupancy sensor
|
£ 290.06 (with 75% efficiency)
£ 30.45
|
130W x 40% x 11 hours x 5 x 52 =
148.7 kWh
|
Toilets |
2.0
(4.0)
|
142.5
(285) |
Ventilation fan with flow rate of 143 to 285 m3/hr
range is recommended.
- Ventilation system to be fitted with controls with on/off
occupancy sensor (Passive Infrared + Timer)
|
£ 50.00
£ 44.10 |
50W x 20% x 11 hours x 5 x 52 =
28.6 kWh
|
Canteen |
6.0
(10.0) |
427.5
(712.5) |
Ventilation fan with flow rate of 428 to 713 m3/hr
with heat recovery system is recommended. (Cost and energy
use is calculated based on fan with maximum flow rate of 550
m3/hr with 70% efficiency)
- Ventilation system to be fitted with controls with CO2
sensor
|
£ 553.33
£ 61.95 |
150W x 30% x 11 hours x 5 x 52 =
128.7 kWh |
Kitchen
|
20.0
(40.0)
|
1425
(2850) |
Ventilation fan with flow rate of 1425 to 2850 m3/hr
with variable speed is recommended.
(Cost and energy use is calculated based on fan with 1650 m3/hr
flow rate)
|
£ 350.00
|
90W x 8 hours x 5 x 52 =
187.2 kWh |
Drying Room |
2.2
|
156.8
|
Ventilation fan with flow rate of 156.8 m3/hr or
more with heat recovery is recommended. (Cost and energy use
is calculated based on fan with maximum flow rate of 220 m3/hr
with 75% efficiency)
- Ventilation system to be fitted with controls with
humidity sensor |
£ 290.06
£ 30.45
|
130W x 24hours x 5 x 52 =
811.2 kWh
|
|
|
|
|
|
|
*Calculated based on minimum required fresh air rate of 5
litres/second per occupant and (based on recommended 8 l/s
per occupant).
**The investment and averaged energy use per annum is
calculated based on information obtained through ventilation
system supplier’s website that best met the required
ventilation rate. |
|
Suppliers of
the recommended ventilation system and control options
|
Ventilation Systems and Control Options Recommended
|
Supplier and contacts
|
Cabin Offices |
Nil |
Nil
|
Meeting Room |
 |
Intervent HRV200WK unit utilises energy efficient AC
external rotor motors. The counter flow heat exchanger
matrix also ensures that the maximum amount of heat is
recovered from the stale exhaust airflow and is utilised to
warm the supply air as it is brought into the building.
Control options include a simple 2-speed switch, Humidisense,
Timesense and Occusense. On average over 75% of heat is
transferred from the stale air to the incoming fresh air.
http://www.admsystems.co.uk |
Toilets |
 |
Code: SDF 100PIR
Model : PIR & Timer
http://www.silavent.co.uk |
Canteen |
  |
Intervent HRV-500
Control options include a simple 2-speed switch and
Occusense.
http://www.admsystems.co.uk |
Kitchen |
 |
VARIO 300/12" ARI-LL-S
Axial Wall/Ceiling Recessed Reversible
[Long Life Motor]
[12in 1650m3/hr] [ABS White]
http://www.vortice.co.uk |
Drying Room |
  |
Intervent HRV-200WK
Control options include a simple 2-speed switch and
Humidisense
http://www.admsystems.co.uk |
|
Back to
Top
Different
types of cabin accommodation requires different ventilation rate for the purpose
of satisfying the minimum safety and health requirements as well as providing
the sufficient level of comfort to the occupants in construction villages. The
ventilation requirements in a cabin accommodation at construction villages can
be evaluated using the methodology above and low energy ventilation systems
could be selected based on the requirements and functional considerations of
each accommodation type. Although providing ventilation to the accommodation
requires energy, the indoor air quality and comfort level could be enhanced and
indirectly will contribute to the increase in productivity and good health of
the workers in construction villages.
Back to
Top
- Kreith, Frank,
West, Ronald E., CRC Handbook of Energy Efficiency, CRC Press, 1997, pg 285 –
291
- McMullan,
Randall, Environmental Science in Building, Fifth Edition, 2002
- Office of the
Deputy Prime Minister, Document F - Ventilation, The Building Regulations
2000, pg 6.
-
The
Carbon Trust, Energy Saving Fact Sheet - Ventilation, May 2005.
-
http://www.admsystems.co.uk
-
http://www.dealec.co.uk
-
http://www.silavent.co.uk
-
http://www.vortice.co.uk
Back to
Top
 |